SIMATIC S7-1200, Analog b, SB 1231, 1 AI, +/-10 V DC (12 bit resol.) or 0-20 mA
|
General inbation
|
Product type designation
|
SB 1231, AI 1x12 bit
|
Supply voltage
|
Rated value (DC)
|
|
● 24 V DC
|
Yes
|
Input current
|
from backplane bus 5 V DC, typ.
|
55 mA
|
Power loss
|
Power loss, typ.
|
0.4 W
|
Analog bs
|
Number of analog bs
|
1; Current or voltage differential bs
|
permissible b voltage for current b (destruction limit), max.
|
±35 V
|
permissible b voltage for voltage b (destruction limit), max.
|
35 V
|
permissible b current for voltage b (destruction limit), max.
|
40 mA
|
permissible b current for current b (destruction limit), max.
|
40 mA
|
Cycle time (all channels) max.
|
156.25 μs; 400 Hz suppression
|
Input ranges
|
● Voltage
|
Yes; ±10V, ±5V, ±2.5V
|
● Current
|
Yes; 0 to 20 mA
|
● Thermocouple
|
No
|
● Resistance thermometer
|
No
|
● Resistance
|
No
|
Input ranges (rated values), voltages
|
● -10 V to +10 V
|
Yes
|
● Input resistance (-10 V to +10 V)
|
≥9 MOhm
|
● -2.5 V to +2.5 V
|
Yes
|
● Input resistance (-2.5 V to +2.5 V)
|
≥9 MOhm
|
● -5 V to +5 V
|
Yes
|
● Input resistance (-5 V to +5 V)
|
≥9 MOhm
|
Input ranges (rated values), currents
|
● 0 to 20 mA
|
Yes
|
● Input resistance (0 to 20 mA)
|
≥ 250 Ohm
|
Analog outputs
|
Number of analog outputs
|
0
|
Cable length
|
● shielded, max.
|
100 m; shielded, twisted pair
|
Analog value generation for the bs
|
Measurement principle
|
integrating
|
Integration and conversion time/resolution per channel
|
● Resolution with overrange (bit including sign), max.
|
11 bit; + sign
|
● Integration time, beterizable
|
Yes
|
● Interference voltage suppression for interference frequency f1 in Hz
|
40 dB, DC to 60 Hz
|
Smoothing of measured values
|
● beterizable
|
Yes
|
● Step: None
|
Yes
|
● Step: low
|
Yes
|
● Step: Medium
|
Yes
|
● Step: High
|
Yes
|
Errors/accuracies
|
Temperature error (relative to b range), (+/-)
|
25 °C ±0.3%, to 55 °C ±0.6% total measurement range
|
Interrupts/diagnostics/status inbation
|
Alarms
|
Yes
|
Diagnostics function
|
Yes
|
Alarms
|
● Diagnostic alarm
|
Yes
|
Diagnostic messages
|
● Wire-break
|
No
|
Diagnostics indication LED
|
● for status of the bs
|
Yes
|
● for maintenance
|
Yes
|
Degree and class of protection
|
Degree of protection acc. to EN 60529
|
|
● IP20
|
Yes
|
Standards, approvals, certificates
|
CE mark
|
Yes
|
CSA approval
|
Yes
|
FM approval
|
Yes
|
RCM (berly C-TICK)
|
Yes
|
Ambient conditions
|
Free fall
|
● Fall height, max.
|
0.3 m; five times, in product package
|
Ambient temperature during operation
|
● min.
|
-20 °C
|
● max.
|
60 °C
|
● horizontal installation, min.
|
-20 °C
|
● horizontal installation, max.
|
60 °C
|
● vertical installation, min.
|
-20 °C
|
● vertical installation, max.
|
50 °C
|
Ambient temperature during storage/transportation
|
● min.
|
-40 °C
|
● max.
|
70 °C
|
Air pressure acc. to IEC 60068-2-13
|
● Operation, min.
|
795 hPa
|
● Operation, max.
|
1 080 hPa
|
● Storage/transport, min.
|
660 hPa
|
● Storage/transport, max.
|
1 080 hPa
|
Relative humidity
|
● Operation at 25 ℃ without condensation, max.
|
95 %
|
Pollutant concentrations
|
● SO2 at RH < 60% without condensation
|
S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
|
Connection b
|
required front connector
|
Yes
|
Mechanics/material
|
Enclosure material (front)
|
|
● Plastic
|
Yes
|
Dimensions
|
Width
|
38 mm
|
Height
|
62 mm
|
Depth
|
21 mm
|
Weights
|
Weight, approx.
|
35 g
|